Service Life Data Query

Use criteria to evaluate potential service life in different HVAC components and building environments.

Matching Buildings 108
Equipment Found 2,255
Criteria
System Type: Miscellaneous

* Equipment with no units, not shown. View full HVAC Equipment List here.

EquipmentTotal UnitsCurrently in ServiceReplaced
UnitsMeanMedianStd Dev95% C.I.MaxMinUnitsMeanMedianStd Dev95% C.I.MaxMin
Computer room air conditioning unit, water-cooled DX compressor94 9113.613.06.63.023.03.0 314.014.05.77.818.010.0
Exhaust fan226 22220.221.08.42.146.0-1.0 418.316.06.87.726.013.0
Domestic hot water heater, electric309 27315.517.58.22.034.0-1.0 3611.812.05.42.526.02.0
Unit heater, electric138 13113.510.08.43.729.03.0 713.012.58.18.021.06.0
Heat recovery unit, air-to-air2 210.010.0n/an/a10.010.0 0n/an/an/an/an/an/a
Refrigeration equipment (ice machines, walk-in coolers/freezers)13 1210.310.58.48.318.02.0 142.042.0n/an/a42.042.0
Domestic hot water heater, natural gas26 2013.18.58.95.035.05.0 615.015.07.07.922.08.0
Fresh Air Units43 4118.921.07.52.834.05.0 216.016.0n/an/a16.016.0
Perimeter heating, supplemental heating810 81024.223.07.14.738.015.0 0n/an/an/an/an/an/a
Other miscellaneous equipment163 15719.420.011.23.546.0-1.0 618.016.07.26.326.08.0
Heat exchanger, plate and frame11 1113.18.08.25.425.05.0 0n/an/an/an/an/an/a
Computer room air conditioning unit, chilled water 268 26817.720.57.84.930.05.0 0n/an/an/an/an/an/a
Baseboard/Finned Tube Radiation100 10018.121.07.84.425.04.0 0n/an/an/an/an/an/a
Fume Hoods/Cabinets1 122.022.0n/an/a22.022.0 0n/an/an/an/an/an/a
Smoke control15 1517.517.53.54.920.015.0 0n/an/an/an/an/an/a
Humidifiers3 17.07.0n/an/a7.07.0 223.023.0n/an/a23.023.0
Cogeneration2 215.015.0n/an/a15.015.0 0n/an/an/an/an/an/a
Heat exchanger, hot water3 338.038.0n/an/a38.038.0 0n/an/an/an/an/an/a
Unit heater, natural gas12 1223.023.51.71.325.021.0 0n/an/an/an/an/an/a
Heat exchanger, heat pipe2 25.05.0n/an/a5.05.0 0n/an/an/an/an/an/a
Dehumidifier, solid dessicant2 1-1.0-1.0n/an/a-1.0-1.0 142.042.0n/an/a42.042.0
Heat exchanger, heat wheel2 1-1.0-1.0n/an/a-1.0-1.0 142.042.0n/an/a42.042.0