System Type: Heating

* Equipment with no units, not shown. View full HVAC Equipment List here.

EquipmentTotal UnitsCurrently in ServiceReplaced
UnitsMeanMedianStd Dev95% C.I.MaxMinUnitsMeanMedianStd Dev95% C.I.MaxMin
Other heating equipment4,234 4,19215.116.09.54.535.0-1.0 4223.225.07.56.634.016.0
Boiler, steel fire-tube, natural draft, hot water11 1117.517.04.13.324.012.0 0n/an/an/an/an/an/a
Boiler, steel water-tube, natural draft, hot water47 3517.919.512.15.640.03.0 1218.018.54.93.923.011.0
2 226.526.54.96.930.023.0 0n/an/an/an/an/an/a
District heating9 929.237.016.410.757.06.0 0n/an/an/an/an/an/a
Boiler, steel fire-tube, forced draft, steam10 1036.838.09.07.946.023.0 0n/an/an/an/an/an/a
Boiler, steel water-tube, forced draft, steam4 437.037.01.01.138.036.0 0n/an/an/an/an/an/a
Boiler, steel water-tube, forced draft, hot water56 4219.615.013.94.851.04.0 1422.621.09.47.033.010.0
Boiler, electric hot water4 419.322.07.67.525.08.0 0n/an/an/an/an/an/a
Boiler, steel fire-tube, forced draft, hot water12 1014.012.07.26.323.07.0 225.025.0n/an/a25.025.0
Boiler, cast iron12 1223.624.09.15.935.04.0 0n/an/an/an/an/an/a
Heat exchanger, horizontal (trench) ground9 813.813.02.71.920.011.0 117.017.0n/an/a17.017.0
Municipal water plant6 610.711.02.21.713.07.0 0n/an/an/an/an/an/a
Heat exchanger, vertical bore214 14411.311.05.71.037.0-16.0 7027.625.013.63.669.04.0
Heat exchanger, ground water, aquifers35 2823.218.512.84.753.07.0 732.021.027.820.688.08.0
Heat exchanger, horizontal ground7 710.911.02.01.413.08.0 0n/an/an/an/an/an/a
Heat exchanger, surface water, closed loop2 211.511.56.48.816.07.0 0n/an/an/an/an/an/a
Heat exchanger, ground water, standing column well6 411.812.01.31.213.010.0 251.551.534.648.076.027.0
Chiller, heat recovery, centrifugal2 125.025.0n/an/a25.025.0 165.065.0n/an/a65.065.0