Service Life Data Query

Use criteria to evaluate potential service life in different HVAC components and building environments.

Matching Buildings 79
Equipment Found 362
Criteria
System Type: Cooling Pump

* Equipment with no units, not shown. View full HVAC Equipment List here.

EquipmentTotal UnitsCurrently in ServiceReplaced
UnitsMeanMedianStd Dev95% C.I.MaxMinUnitsMeanMedianStd Dev95% C.I.MaxMin
Centrifugal pump, close-coupled, end-suction89 8918.820.06.72.442.07.0 0n/an/an/an/an/an/a
Centrifugal pump, split-case, single stage133 13320.621.09.22.438.05.0 0n/an/an/an/an/an/a
Centrifugal pump, frame-mounted, end-suction111 11119.121.09.23.035.03.0 0n/an/an/an/an/an/a
Centrifugal pump, split-case, multistage pump12 719.026.013.915.728.03.0 542.042.0n/an/a42.042.0
Condensate pump7 46.35.04.24.711.03.0 323.523.53.54.926.021.0
Centrifugal pump, vertical in-line10 1017.918.06.85.032.012.0 0n/an/an/an/an/an/a