Service Life Data Query
Use criteria to evaluate potential service life in different HVAC components and building environments.
Matching Buildings
79
Equipment Found
362
Criteria
System Type: Cooling Pump
* Equipment with no units, not shown. View full HVAC Equipment List here.
| Equipment | Total Units | Currently in Service | Replaced | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Units | Mean | Median | Std Dev | 95% C.I. | Max | Min | Units | Mean | Median | Std Dev | 95% C.I. | Max | Min | ||
| Centrifugal pump, close-coupled, end-suction | 89 | 89 | 18.8 | 20.0 | 6.7 | 2.4 | 42.0 | 7.0 | 0 | n/a | n/a | n/a | n/a | n/a | n/a |
| Centrifugal pump, split-case, single stage | 133 | 133 | 20.6 | 21.0 | 9.2 | 2.4 | 38.0 | 5.0 | 0 | n/a | n/a | n/a | n/a | n/a | n/a |
| Centrifugal pump, frame-mounted, end-suction | 111 | 111 | 19.1 | 21.0 | 9.2 | 3.0 | 35.0 | 3.0 | 0 | n/a | n/a | n/a | n/a | n/a | n/a |
| Centrifugal pump, split-case, multistage pump | 12 | 7 | 19.0 | 26.0 | 13.9 | 15.7 | 28.0 | 3.0 | 5 | 42.0 | 42.0 | n/a | n/a | 42.0 | 42.0 |
| Condensate pump | 7 | 4 | 6.3 | 5.0 | 4.2 | 4.7 | 11.0 | 3.0 | 3 | 23.5 | 23.5 | 3.5 | 4.9 | 26.0 | 21.0 |
| Centrifugal pump, vertical in-line | 10 | 10 | 17.9 | 18.0 | 6.8 | 5.0 | 32.0 | 12.0 | 0 | n/a | n/a | n/a | n/a | n/a | n/a |