Service Life Data Query

Use criteria to evaluate potential service life in different HVAC components and building environments.

Matching Buildings 287
Equipment Found 935
Criteria
System Type: Cooling

* Equipment with no units, not shown. View full HVAC Equipment List here.

EquipmentTotal UnitsCurrently in ServiceReplaced
UnitsMeanMedianStd Dev95% C.I.MaxMinUnitsMeanMedianStd Dev95% C.I.MaxMin
Chiller, centrifugal239 20917.618.08.21.541.03.0 3025.225.07.63.342.07.0
Chiller, air-cooled rotary (screw)9 812.38.510.38.232.05.0 123.023.0n/an/a23.023.0
Other cooling equipment369 36516.320.010.25.034.0-1.0 420.520.55.25.125.016.0
4 25.05.0n/an/a5.05.0 220.020.0n/an/a20.020.0
Chiller, water-cooled reciprocating9 920.617.011.28.335.06.0 0n/an/an/an/an/an/a
Chiller, absorption, indirect-fired, single-stage6 638.038.00.00.038.038.0 0n/an/an/an/an/an/a
Chiller, air-cooled reciprocating16 1524.028.514.38.137.04.0 111.011.0n/an/a11.011.0
Chiller, water-cooled rotary (screw)5 511.011.07.19.816.06.0 0n/an/an/an/an/an/a
Municipal water plant7 710.310.02.21.613.07.0 0n/an/an/an/an/an/a
District cooling8 37.38.01.21.38.06.0 536.036.022.631.452.020.0
Heat exchanger, horizontal (trench) ground8 714.113.02.72.020.012.0 117.017.0n/an/a17.017.0
Heat exchanger, vertical bore195 14211.511.05.20.937.0-1.0 5327.125.013.83.769.04.0
Heat exchanger, ground water, aquifers37 3023.518.513.14.753.07.0 732.021.027.820.688.08.0
Chiller, heat recovery, centrifugal2 221.521.54.96.925.018.0 0n/an/an/an/an/an/a
Heat exchanger, horizontal ground7 710.911.02.01.413.08.0 0n/an/an/an/an/an/a
Heat exchanger, surface water, closed loop2 211.511.56.48.816.07.0 0n/an/an/an/an/an/a
Heat exchanger, ground water, standing column well6 411.812.01.31.213.010.0 251.551.534.648.076.027.0