Service Life Data Query

Use criteria to evaluate potential service life in different HVAC components and building environments.

Matching Buildings 344
Equipment Found 27,752
Criteria
System Type: Air Distribution

* Equipment with no units, not shown. View full HVAC Equipment List here.

EquipmentTotal UnitsCurrently in ServiceReplaced
UnitsMeanMedianStd Dev95% C.I.MaxMinUnitsMeanMedianStd Dev95% C.I.MaxMin
Air handling unit, constant volume206 18425.927.011.94.846.06.0 2234.740.020.523.252.012.0
Air handling unit, variable air volume962 89318.620.08.81.847.0-20.0 6928.226.012.46.364.012.0
Packaged DX unit, water-cooled187 17714.817.09.04.335.04.0 1022.022.0n/an/a22.022.0
Packaged DX unit, air-cooled32 3214.115.07.04.127.06.0 0n/an/an/an/an/an/a
Heat pump, water-source1,484 1,37917.521.07.12.927.04.0 10516.516.50.71.017.016.0
Air handling unit, variable volume, variable temperature196 6120.121.59.25.234.04.0 13512.012.0n/an/a12.012.0
Other air distribution equipment3,089 3,02713.611.012.25.651.0-1.0 6220.520.56.48.825.016.0
Split DX system174 17317.919.04.93.224.07.0 117.017.0n/an/a17.017.0
Air handling unit, dual duct20 2036.537.06.65.345.025.0 0n/an/an/an/an/an/a
Packaged DX unit, rooftop220 21515.616.06.82.137.03.0 521.322.05.45.327.014.0
Air handling unit, multizone229 22930.424.518.48.576.06.0 0n/an/an/an/an/an/a
Fan coil unit2,884 1,60526.827.013.86.151.06.0 1,27936.536.524.419.565.04.0
Heat pump, air-to-air1,296 1,29514.114.05.74.220.03.0 117.017.0n/an/a17.017.0
Heat pump, water-to-air, geothermal application15,090 11,36811.912.05.40.837.05.0 3,72227.625.013.53.669.08.0
Heat pump, water-to-water, geothermal application28 2812.013.01.72.013.010.0 0n/an/an/an/an/an/a
Air handling unit, single zone87 8721.718.512.57.744.010.0 0n/an/an/an/an/an/a
Residential furn. and pkg'ed condensing unit/heat pump132 13231.031.0n/an/a31.031.0 0n/an/an/an/an/an/a
Packaged terminal air conditioner/heat pump231 23127.027.014.119.637.017.0 0n/an/an/an/an/an/a